Chinese English

Contact Us Now! foreign_trade@0086pv.com

PTFE lined with double pipe fire retarding breathing valve

Product Category:BREATHER VALVE
Product Name:PTFE lined with double pipe fire retarding breathing valve
Product Tag:PTFE lined with double pipe fire retarding breathi
Update Date:2021/8/31 0:04:24
Visits:

Note: Our Products Can Be Customized According To Customers' Needs. In Addition To National Standards,We Can Design And Manufacture According To American Standards, Japanese Standards, German Standards, Russian Standards, British Standards And So On.

1. Product introduction of fluorine-lined breathing valve

According to the standard "Code for Fire Protection Design of Petrochemical Enterprises" (GB50160-90), "Fixed roof tanks for Class A and Class B liquids should be equipped with flame arresters and breathing valves." It can be seen that the breathing valve and flame arrestor are indispensable facilities for the storage tank. It can not only maintain the pressure balance of the storage tank, ensure that the storage tank is not damaged under overpressure or vacuum, but also reduce the volatilization and loss of the medium in the tank. The breathing valve is Energy-saving products that maintain the air pressure balance of the storage tank and reduce the volatilization of the medium are often used in conjunction with flame arresters.

The fire-resistance breathing valve produced by our company has the characteristics of compact structure, large ventilation, small leakage, corrosion resistance, and good sealing performance. Recently, a high-level fluorine-lined breathing valve (type HXF-IZ) and flame arrester have been developed. It is located at the suction port of the breathing valve to prevent fire sources from entering the breathing valve housing. It has the advantages of small size, light weight, convenient maintenance, cleaning, and replacement.

2. Technical parameters of fluorine-lined breathing valve

1. Operating pressure of breathing valve:

Type A: 355Pa (36mmH2O), -295Pa (-30mmH2O)

Type B: 980Pa (100mmH2O), -295 Pa (-30mmH2O)

Type C: 1750Pa (180mmH2O), -295 Pa (-30mmH2O)

Type D: Special pressure, user specified.

2. Material of fire barrier: stainless steel 316/Hastelloy.

3. Explosion-proof level: BS 5501; IIB, IIC.

4. Flange standards: GB, HG, SH, HGJ, JB, ANSL, JIS and other standards. (Specified by the user, please indicate the pressure level)

5. Manufacturing and testing standards: Manufacture and acceptance according to (petroleum storage tank breathing valve) SY7511-87, (petroleum storage tank flame arrestor fire resistance performance and test methods) GB5908-86 and other standards: or user-specified standards.

Note: The above product pictures and dimensions are for reference only. If you need accurate drawings, please contact us.

3. Maintenance of fluorine-lined breathing valve

1. After the breathing valve products are delivered to the construction site, if they are not installed temporarily or the factory will be overhauled or overhauled in the future, they should be stored in a warehouse with rainproof facilities: the breathing valve series products must not be inverted during transportation.

2. The breathing valve series products should be checked on the tank top once a month to check whether there is dust or dirt in the valve disc, valve seat, valve stem, valve sleeve, etc. If there is, clean it up: give the valve sleeve and valve every six months. Wipe the rod again with transformer oil.

3. Check the fire barrier of the breathing valve of the flame arrester once every six months. If stains or impurities are found to block the fire barrier, remove the fire barrier, use the corresponding solvent to clear the stain, and then clean the fire barrier with water Clean, put it in the shell after ventilating and drying.

Four, fluorine-lined breathing valve ordering instructions

Please specify the size, operating pressure and material of the fluorine-lined breathing valve when ordering. When other standard flanges, materials or operating pressures are required, please specify when ordering.

INQUIRY

© Copyright 2002 - 2021 | Shanghai Wuyue Pump & Valve Group Co., Ltd. | All Rights Reserved Sitemap ICP:09023850-8 Design By CNPV